Hi,

I am in Australia and I know Ecosol solar is not common in UK.
I am still giving a try if someone here can help with this.

I am running Ecosol/Kustos set-up.
I finished setting with a jumper on for constant power and it works fine with the jumper on.

However, without jumper it opens and closes only 1/3 of full operation.
What may cause this?
(09-03-2022, 11:51 AM)supremee Wrote: [ -> ]Hi,

I am in Australia and I know Ecosol solar is not common in UK.
I am still giving a try if someone here can help with this.

I am running Ecosol/Kustos set-up.
I finished setting with a jumper on for constant power and it works fine with the jumper on.

However, without jumper it opens and closes only 1/3 of full operation.
What may cause this?

Hi ,
I am facing the same issue. Did you find the soltuion?

Thanks
(09-03-2022, 11:51 AM)supremee Wrote: [ -> ]Hi,

I am in Australia and I know Ecosol solar is not common in UK.
I am still giving a try if someone here can help with this.

I am running Ecosol/Kustos set-up.
I finished setting with a jumper on for constant power and it works fine with the jumper on.

However, without jumper it opens and closes only 1/3 of full operation.
What may cause this?
Have got the solution to it. In logic you will have Aux 0/1/2/3 - make sure the value is 6-gate running ( output active while motors are powered) 

Thanks